Direct Conclusion
Scaling manifests as reduced heat transfer with normal flow, while clogging causes increased pressure drop and reduced flow; both often occur simultaneously.
Judgment Criteria
- 01
Compare inlet/outlet pressure differential and flow: If the differential rises significantly while flow drops, check for blockages or foreign objects first.
- 02
Compare the terminal temperature difference with outlet temperature: if flow is normal but the terminal temperature difference increases, scaling on the heat exchange surface is likely.
Responsibility and Timeliness
Reviewer: Enterprise Technical Team
Content updated: 2025-06
Publisher: Shandong Zhengyi International Trade Co., Ltd.
Contact: 13305317997
Content is compiled based on product technical documentation and field experience. Actual operating conditions are subject to site confirmation and contractual agreements.
What should I do if the heat exchanger is fouled?
NextWhat causes the cooling water outlet temperature to keep rising?
Doesn't this answer match your live response?
Provide pipe diameter, flow rate, and water temperature for technical assessment based on operating conditions.